☆ introduce 

Indoor High Voltage Vacuum Circuit Breaker

ZN28-12K




1.General  Description

ZN28-12K fixed type indoor MV vacuum breaker is used for many kinds of switchgears

like XGN2-t2 (Z). It is widely used  for 12kV voltage systems  which  is accordance with GB1984-2003 standards.

Structural characteristics:

1.This vacuum circuit breaker adopts air insulation.lt can meet air distance and creepage under normal run condition.

2.The operating mechanism can use CD17 or CT19 type mechanism,the outlet curve has good adaptation for vacuum interrupters.lt has high reliable with characteristics of long life and easy maintenance.

3.Convenient for matching with switchgear;convenient and reliable operation;compulsive mechanical interlock way is adopted;meet “Five Prevention” function.

2.Applying  conditions:

Ambient temperature;-10----+40

Relative humidity:daily average ≤95%,monthly average ≤90%

 Seismic intensity ≤8

Saturated vapor pressuredaily average ≤2.2kPamonthly average≤1.8kPa

Altitude:≤1000m;(Not including special requirement

Service environmentshould be avoided fire, explosion risk, serious pollution, chemical corrosion and violent vibration

3.Technical specification

No.

Item

Unit

Data

1

Rated voltage

kV

12

2

Rated frequency

Hz

50/60

3

Rated power frequency withstand voltage/1min

kV

42

4

Rated lighting impulse withstand voltage

kV

75

5

Rated current

A

630

1250

1600

2000

2500

3150

6

Rated short circuit breaking current                  Rated short time withstand   current(4s)

kA

20






25

25






31.5

31.5

31.5

31.5




40

40

40

40

7

Rated short circuit making current(peak)               Rated withstand current(peak)

kA

50






63

63





80

80

80

80

80



100

100

100

100

100

8

Mechanical life

Times

10000

9

Rated duration of short circuit

s

4

10

Rated operating sequence


O-0.3s-CO-180s-CO

O-180s-CO-180s-CO(40kA以上)

11

Rated short circuit breaking times

Times

30

12*

Rated single capacitor bank breaking current

A

400

13*

Rated back to back capacitor bank breaking current

A

400

14

Clearance between open contacts

mm

11 ± 1

15

Over-travel of contact

mm

4 ± 1

16

Opening &closing simultaneity of 3 phase contact

ms

≤ 2

17

Bounce time of contact closed

ms

≤ 2

18

Closing time

ms

50~100

19

Opening time

ms

20~60

20

Average closing speed

ms

0.6 ± 0.2

21

Average opening speed   

m/s

1.1 ± 0.2

22

Max DC component


50%



4.Overall drawing